Analog HART input | RSD-CI-Ex8.H

Артикул: RSD-CI-Ex8.H
Производитель: Pepperl-Fuchs



  • 8-channel
  • Inputs EEx ia IIC
  • Device installation in Zone 1, Zone 2, or Zone 22
  • Module can be exchanged under voltage in Zone 1 (hot swap)
  • Inputs for 2-wire and 3-wire transmitters
  • Transfer of HART signals into the hazardous area
  • Lead breakage (LB) monitoring and short-circuit (SC) monitoring for each field circuit
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: RSD-CI-Ex8.H

Supply
Connectionterminals 34, 50 V+; 35, 51 V-
Rated voltage8.88 ... 9.5 V
Power loss3.9 W
Power consumption7 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus
Cycle time1.6 ms
Input
Connectionterminals 0+, 1 sig, 2-; 4+, 5 sig, 6-; 8+, 9 sig, 10-; 12+, 13 sig, 14-; 17+, 18 sig, 19-; 21+, 22 sig, 23-; 25+, 26 sig, 27-; 29+, 30 sig, 31-
Input signal0 ... 25 mA (3-wire) ; 4 ... 22 mA (2-wire)
Transmitter supply voltage17 V at 20 mA
Line fault detectionbreakage I ≤ 2 mA, short-circuit I > 22 mA
Transfer characteristics
Resolution16 Bit
Step response60 ms (0 ... 90 % of the measured value by smallest filter setting)
Deviation0.1 % of input signal range at 25 В°C (298 K)
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007, EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Core cross-sectionmax. 2.5 mm2
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 250 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 98 ATEX E 017 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)2G EEx ia/ib IIB/IIC
II (1D)(2D)
Temperature classT4
Supplyonly in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34
Input
Voltage24.4 V
Current92.5 mA
Power565 mW
External capacitance119 nF
External inductance4 mH
Internal capacitancenegligible
Internal inductancenegligible
Internal buscustomer specific
Statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3D IP54 T 90В°C
Electrical isolation
Input/inputno electrical isolation
Input/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Input/Internal Bussafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Internal bus/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V