ControlNet LWL adapter | RSD-FC-Ex2.CN.3km

Артикул: RSD-FC-Ex2.CN.3km
Производитель: Pepperl-Fuchs



  • Converts the TTL signals of the ControlNet copper/fiber optic adapter into LWL signals
  • LWL channels: EEx ia IIC
  • Device installation in Zone 1, Zone 2, or Zone 22
  • Transfer range up to 3 km
  • Transfer rate 5 MBits/s
  • Two bi-directional fiber optic connections
  • Power supply channel via the copper/fiber optic adapter

Datasheet as PDF in following languages:


Technical Data: RSD-FC-Ex2.CN.3km

Supply
Connection30-pin bus connector
Internal bus
ConnectionTTL bus
Interfacemanufacturer specific bus
External bus
Connectionfiber optic cable
InterfaceControlNet international version 1.5, intrinsically safe
Transfer rate5 MBit/s
Fiber optic type62.5/125 micron
Fiber optic connectionST (ceramic)
Fiber optic wave length1300 nm
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007 , EN 60079-26:2007
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Climatic conditionsDIN IEC 721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typefiber optic cable
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 140 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 99 ATEX 010 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)2G EEx ia/ib IIB/IIC
Temperature classT4
Supplyonly in connection with RSD-CFA-Ex.CN
Internal buscustomer specific
Statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3D IP54 T 90В°C
Electrical isolation
Internal/external bussafe galvanic isolation acc. to EN 60079-11:2007
Internal bus/power supplyno electrical isolation
External bus/power supplysafe galvanic isolation acc. to EN 60079-11:2007