ControlNet gateway | RSD-GW-Ex2.CN
Артикул: RSD-GW-Ex2.CN
Производитель: Pepperl-Fuchs
|
|
- Connects the IS-RPI system to the control system via ControlNet
- Fieldbus intrinsically safe EEx ib IIC
- Device installation in Zone 1, Zone 2, or Zone 22
- Up to 24 gateways on one intrinsically safe bus network
- ControlNet international version 1.5 (intrinsically safe)
- Redundant coaxial transfer options possible
- Up to 8 I/O modules on one gateway via the backplane bus
- LED status indication
- Gateway can be replaced under voltage in zone 1 (hot swap)
- EMC acc. to NAMUR NE 21
Datasheet as PDF in following languages: Technical Data: RSD-GW-Ex2.CNSupply | Connection | terminals V+, V- | Rated voltage | 8.88 ... 9.5 V | Power loss | 8 W | Power consumption | 8.5 W | Internal bus | Connection | backplane bus | Interface | manufacturer specific bus | Cycle time | 1.6 ms | External bus | Connection | BNC connection A, B | Interface | ControlNet international version 1.5, intrinsically safe | Transfer rate | 5 MBit/s | Bus address | 1 ... 99 , adjustable via switch | Directive conformity | Electromagnetic compatibility | | | Directive 2004/108/EC | EN 61326-1:2006 | Explosion protection | | | Directive 94/9/EC | EN 60079-0: 2006, EN 60079-11: 2007 | Standard conformity | Insulation coordination | EN 50178 | Electrical isolation | EN 60079-11:2007 | Electromagnetic compatibility | NE 21:2006 | Protection degree | IEC 60529 | Climatic conditions | IEC 60721 | Ambient conditions | Classification | 3K3 | Ambient temperature | -20 ... 70 В°C (-4 ... 158 В°F) | Storage temperature | -20 ... 100 В°C (-4 ... 212 В°F) | Relative humidity | 95 % non-condensing | Shock resistance | 15 g peak, 11 ms period | Vibration resistance | 2 g , 10 ... 500 Hz according to IEC 60068-2-6 | Damaging gas | acc. to ISA-S71.04-1985, severity level G3 | Mechanical specifications | Connection type | terminals, BNC connection | Core cross-section | max. 2.5 mm2 | Protection degree | IP20, for on-site installation a separate housing is required with a minimum of IP54 | Mass | approx. 350 g | Mounting | DIN rail mounting | Data for application in connection with Ex-areas | EC-Type Examination Certificate | DMT 99 ATEX E 007 X , for additional certificates see www.pepperl-fuchs.com | | Group, category, type of protection | II 2 G Ex ib IIC T4 | | Temperature class | | Supply | only in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34 | External bus | | | Voltage | 5.4 V | | Current | 160 mA | Internal bus | customer specific | Electrical isolation | | | Internal/external bus | no electrical isolation | | Internal bus/power supply | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V | | External bus/power supply | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |
|
Назад в раздел
|