ControlNet barrier | RS-FB-Ex2.CN

Артикул: RS-FB-Ex2.CN
Производитель: Pepperl-Fuchs



  • Connects the intrinsically safe ControlNet with the non-intrinsically safe ControlNet
  • Fieldbus intrinsically safe EEx ib IIC
  • Device installation not in hazardous areas
  • ControlNet up to 5 MBit/s

Datasheet as PDF in following languages:


Technical Data: RS-FB-Ex2.CN

Input
ConnectionBNC connection
Input signalControlNet international version 1.5
Output
ConnectionBNC connection
Output signalControlNet international version 1.5, intrinsically safe
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007 , EN 60079-25: 2004
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeBNC connection
Protection degreeIP20
Mass175 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 99 ATEX E 058 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (2)G [EEx ib] IIC
Supply
Maximum safe voltage253 V
Output
Voltage7 V
Current55 mA at 52 kHz
Electrical isolation
Input/Outputno electrical isolation
Output/Outputno electrical isolation


Назад в раздел