PROFIBUS DP V1-Gateway HART | RSD-GW3-Ex2.DPE.ED

Артикул: RSD-GW3-Ex2.DPE.ED
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • Connects the IS-RPI system with the control system via PROFIBUS DP
  • Fieldbus intrinsically safe EEx ib IIC
  • Device installation in Zone 1, Zone 2, or Zone 22
  • Up to 10 gateways on one intrinsically safe bus network
  • PROFIBUS DP V1 up to 1.5 MBit/s
  • Up to 8 I/O modules on one gateway via the backplane bus
  • PROFIBUS DP media redundancy
  • Transfer of HART signals
  • LED status indication
  • Channel specific PROFIBUS diagnosis
  • Gateway can be replaced under voltage in zone 1 (hot swap)
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: RSD-GW3-Ex2.DPE.ED

Supply
Connectionterminals V+, V-
Power loss8 W
Power consumption8.5 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus
Cycle time1.6 ms
External bus
Connectionterminals 1+, 2-
InterfacePROFIBUS with intrinsically safe RS 485 transfer technique
Transfer rate9.6 ... 1500 kBit/s
Bus address1 ... 99 , adjustable via switch
Terminating impedanceadjustable with sliding switch: I = OFF; ON = ON
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Explosion protection
Directive 94/9/ECEN 50014, EN 50020, EN 50281-1-1
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 50020
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-20 ... 100 °C (-4 ... 212 °F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Core cross-sectionmax. 2.5 mm2
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 325 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 00 ATEX 023 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II 2G EEx ib IIC
II (2D)
Temperature classT4
Supplyonly in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34
External bus
Voltage± 3.72 V
Current76.5 mA
Power103 mW
Voltage± 3.75 V
Internal capacitancenegligible
Internal inductancenegligible
External capacitance100 µF
External inductance1.5 mH
L/R-ratio344 µH/Ω
Internal buscustomer specific
Statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3D IP54 T 90°C
Electrical isolation
Internal/external busno electrical isolation
Internal bus/power supplysafe galvanic isolation acc. to EN 50020, voltage peak value 60 V
External bus/power supplysafe galvanic isolation acc. to EN 50020, voltage peak value 60 V


Назад в раздел