Артикул: RSD-TI-Ex8
Производитель: Pepperl-Fuchs
Not available for purchase, If you need assistance please contact us sales@sm-industry.ru Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru
8-channel Inputs EEx ia IIC Device installation in Zone 1, Zone 2, or Zone 22 Module can be exchanged under voltage in Zone 1 (hot swap) Connection of resistance thermometers Pt100 or Ni100 in 2-, 3- or 4-wire connection Connection of thermocouples, type B, E, J, K, L, N, R, S or T Connection of other resistive sensors, mV sources or thermocouples possible. Linearization adjustable via software Lead breakage (LB) monitoring for each field circuit Filter cut-off frequency can be programmed from 0.2 Hz to 600 Hz EMC acc. to NAMUR NE 21
Datasheet as PDF in following languages:
Technical Data: RSD-TI-Ex8 Supply Connection terminals 34, 50 V+; 35, 51 V- Rated voltage 8.88 ... 9.5 V Power loss 1.6 W Power consumption 1.6 W Internal bus Connection backplane bus Interface manufacturer specific bus Cycle time 1.6 ms Input Connection terminals 0+, 1H, 2L, 3-; 4+, 5H, 6L, 7-; 8+, 9H, 10L, 11-; 12+, 13H, 14L, 15-; 17+, 18H, 19L, 20-; 21+, 22H, 23L, 24-; 25+, 26H, 27L, 28-; 29+, 30H, 31L, 32- Input signal suitable for: Pt100, Pt200, Ni100, Ni200, Ni120 Minco, Cu10 Minco thermocouples type B, E, J, K, N, R, S, T and mV sources Lead resistance max. 10 Ω for each connection Line fault detection lead monitoring for all lines and CJC Transfer characteristics Resolution 16 Bit Step response 17 ms (0 ... 90 % of the measured value by smallest filter setting) Directive conformity Electromagnetic compatibility Directive 2004/108/EC EN 61326-1:2006 Explosion protection Directive 94/9/EC EN 60079-0: 2006, EN 60079-11: 2007, EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006 Standard conformity Insulation coordination EN 50178 Electrical isolation EN 60079-11:2007 Electromagnetic compatibility NE 21:2006 Protection degree IEC 60529 Climatic conditions IEC 60721 Ambient conditions Classification 3K3 Ambient temperature -20 ... 70 °C (-4 ... 158 °F) Storage temperature -20 ... 100 °C (-4 ... 212 °F) Relative humidity 95 % non-condensing Shock resistance 15 g peak, 11 ms period Vibration resistance 2 g , 10 ... 500 Hz according to IEC 60068-2-6 Damaging gas acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Connection type Terminals Core cross-section max. 2.5 mm2 Protection degree IP20, for on-site installation a separate housing is required with a minimum of IP54 Mass approx. 245 g Mounting DIN rail mounting Data for application in connection with Ex-areas EC-Type Examination Certificate DMT 98 ATEX E 015 X , for additional certificates see www.pepperl-fuchs.com Group, category, type of protection II (1)2G EEx ia/ib IIB/IIC II (1D)(2D)Temperature class T4 Supply only in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34 Input Voltage 9 V Current 38 mA Power 86 mW External capacitance 4.9 µF External inductance 20 mH L/R-ratio 0.4 mH/Ω Internal bus customer specific Statement of conformity Group, category, type of protection, temperature class II 3D IP54 T 90°CElectrical isolation Input/input no electrical isolation Input/power supply safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V Input/Internal Bus safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V Internal bus/power supply safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V