Solenoid Driver | KFD2-SD-Ex1.48.90A

Артикул: KFD2-SD-Ex1.48.90A
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 1-channel
  • Output EEx ia IIC
  • Device installation in Zone 2
  • Up to SIL3 acc. to IEC 61508

Datasheet as PDF in following languages:


Technical Data: KFD2-SD-Ex1.48.90A

Product Description
current limit 45 mA
Supply
Rated voltageloop powered
Power loss1.3 W
Input
Connectionterminals 7+, 8-
Rated voltage5 ... 35 V DC
Current7 mA at 18.5 V nominal supply voltage,
85 mA at 35 V nominal supply voltage
Output
Internal resistormax. 294 Ω
Limitcurrent IE: min. 45.3 mA
voltage UE: 9.1 V
Open loop voltagemin. 22.8 V
Connectionterminals 1+, 2-
Output rated operating current45 mA
Output signalThese values are valid for the rated operating voltage 20 ... 35 V DC.
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326, EN 50081-2
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) , housing type B1
Data for application in connection with Ex-areas
EC-Type Examination CertificateBAS 00 ATEX 7216 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC (-20 В°C ≤ Tamb ≤ 60 В°C) [circuit(s) in zone 0/1/2]
Statement of conformityTГњV 99 ATEX 1499 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4 [device in zone 2]
Directive conformity
Directive 94/9/ECEN 50014, EN 50020, EN 50021