Transmitter Power Supply | KFD2-CRG-1.D

Артикул: KFD2-CRG-1.D
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • 2-wire transmitters or current sources
  • Output 0/4 mA ... 20 mA
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable by PACTwareTM or keypad
  • Line fault detection (LFD)
  • Up to SIL2 acc. to IEC 61508

Datasheet as PDF in following languages:


Technical Data: KFD2-CRG-1.D

Product Description
24 V DC:
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage20 ... 30 V DC
Rated currentapprox. 100 mA
Power loss2 W
Power consumption2.5 W
Input
Connectionterminals 1, 2, 3
Input I
Input signal0 ... 20 mA
Available voltage≥ 15 V at 20 mA
Open circuit voltage/short-circuit current24 V / 33 mA
Input resistance45 Ω (terminals 2, 3)
Lead monitoringbreakage I < 0.2 mA; short-circuit I > 22 mA acc. to NAMUR NE43
Output
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output: analog terminals 8+, 7-
Output signal0 ... 20 mA or 4 ... 20 mA
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIISignal, analog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 50081-2, EN 50082-2
Conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3


Назад в раздел