Signal Converter | KFD2-UT-1-1

Артикул: KFD2-UT-1-1
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 1-channel
  • 24 V DC nominal supply voltage
  • Accuracy ± 0.1 %
  • Adjustment option of temperature measuring range for Pt100, Ni100 in 2-, 3- or 4-wire versions
  • Adjustment option of thermocouple (B, E, J, K, L, N, R, S or T)
  • Freely definable characteristic curve for resistance 0 Ω ... 400 Ω and voltage -50 mV ... +150 mV
  • Internal/External cold junction compensation
  • Sensor burnout monitoring for thermocouples
  • Sensor burnout and short-circuit monitoring (SC) for Pt100
  • Online adjustments via serial interface to PC
  • Factory set on request
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KFD2-UT-1-1

Product Description
Voltage output 1 V ... 5 V
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power loss0.85 W
Power consumptionmax. 1.5 W
Input
Connectionterminals 1, 2, 3 and 4
suitable for Pt100, Ni100, thermocouples type B, E, J, K, L, N, R, S or T (IEC 584)
configuration via programming jack
Lead resistancemax. 50 Ω per lead
Measuring currentapprox. 400 µA with resistance measuring sensor
current for lead breakage monitoring switched off during the measurement
Output
Connectionterminals 7-, 8+
voltage output
1 ... 5 V; 5,125 V
at input signal overrange
Loadmin. 10 kΩ
Fault signaldownscale 0.5 ... 1 V (programmable) or
upscale 5.025 ... 5.125 V (programmable)
Output resistancemax. 10 Ω
Transfer characteristics
Reaction time≤ 430 ms
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Massapprox. 110 g


Назад в раздел