Output Isolator | LB4101A

Артикул: LB4101A
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 1-channel
  • Output Ex ia
  • Analog output module for 0/4 mA ... 20 mA
  • Installation in Zone 2, Zone 22, Div. 2, or safe area
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Module can be exchanged under voltage (hot swap)

Datasheet as PDF in following languages:


Technical Data: LB4101A

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power consumption0.73 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus to standard com unit/bus coupler
Output
Number of channels1
Connectionterminals 2+, 3+ / 4-, 5-
Current4 ... 20 mA (0 ... 25 mA)
short-circuit protected
Load750 Ω max.
Line fault detectionmin. 1 mA
Response thresholdmin. 850 Ω
Watchdogoutput off 0.5 s after serious fault
Transfer characteristics
Deviation0.1 % of the input signal range at 20 В°C (68 В°F)
Refresh timeapprox. 50 ms
Indicators/settings
LED indicatorLED green: supply
LED red: line fault
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasfor plugs: 21 days in 25 ppm SO2, at 25 В°C and 75 % rel. humidity, device G3
Mechanical specifications
Protection degreeIP20 (module) , mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 90 g
Dimensions16 x 100 x 103 mm (0.63 x 3.9 x 4 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 03 ATEX 2042 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1) G [Ex ia] IIC,
Ex-Hexagon II (1) D [Ex iaD]
Declaration of conformityPF 08 CERT 1234 X
Group, category, type of protection, temperature classEx-Hexagon II 3 G Ex nA IIC T4
Electrical isolation
Output/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0, EN 60079-11, EN 60079-15, EN 60079-26, EN 61241-0, EN 61241-11
International approvals
UL approvalE106378
IECEx approvalBVS 09.0037X , BVS 08.0011X


Назад в раздел