Voltage Repeaters | KFD2-VR-Ex1.50m.L

Артикул: KFD2-VR-Ex1.50m.L
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 1-channel
  • Input EEx ia IIC
  • Device installation in Zone 2
  • 24 V DC nominal supply voltage
  • Lead breakage monitoring of the input circuit (L versions)
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KFD2-VR-Ex1.50m.L

Product Description
Transmission range 0 mV ... ± 50 mV
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage10 ... 40 V DC
Ripplewithin the supply tolerance
Rated current≤ 7 mA
Power loss/power consumption≤ 0.28 W
Input
Connectionterminals 4+, 5-
Input resistancemax. 20 MΩ (10 MΩ for .L- and .R version) , see also additional information
Transmission range0 ... ± 50 mV
Offset voltage/current≤ 5 µV / ≤ 5 nA
Output
Connectionterminals 7+, 8-
LoadAccuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ
Voltage0 ... ± 50 mV
Output resistancemax. 3 Ω
Line fault detection-80 mV
Transfer characteristics
Trip value-3 db at 350 Hz
Absolute< 0.25 K at 40 V voltage supply
Rise time≤ 1 ms
Directive conformity
Electromagnetic compatibilityStandards
Directive 89/336/EECon request
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Massapprox. 125 g
Data for application in connection with Ex-areas
EC-Type Examination CertificateBASEEFA 03 ATEX 0076 ; for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection[EEx ia] IIC (Tamb = 60 В°C)
Statement of conformityTГњV 99 ATEX 1499 X (observe statement of conformity)
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4
Directive conformityStandards
Directive 94/9/ECon request