MODBUS Plus gateway, baseline | KSD2-GW-MPL.485B

Артикул: KSD2-GW-MPL.485B
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • Connects the Remote Process Interface to the control system/PLC/PC via MODBUS Plus
  • Couples the internal CAN bus to the external MODBUS Plus
  • Device installation in Zone 2
  • For the connection of max. 16 RPI devices
  • Master function for the internal CAN bus
  • External bus: MODBUS Plus
  • External baud rate 1 MBd
  • Standard interface RS 485
  • Separate service connection independent from the DCS or PLC through RS 485 interface in addition to MODBUS Plus connection
  • 24 V DC nominal supply voltage
  • Redundancy of the gateways and external buses not possible
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KSD2-GW-MPL.485B

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power consumption4.8 W
Internal bus
ConnectionPower Rail
InterfaceCAN protocol via Power Rail bus with up to 16 units
Cycle time1 device 25 ms
16 devices with discrete input 29 ms
16 devices with discrete output 33 ms
16 devices with analog input 31 ms
16 devices with analog output 35 ms
External bus
Connection9-pin Sub-D socket
InterfaceMODBUS Plus, RS 485 interface
Service interface
Connectionterminals 22, 23, 24
InterfaceRS 485
Electrical isolation
Internal/external busbasic insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff AC
Internal bus/power supplynot available
External bus/power supplybasic insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff AC
Service interface/internal busbasic insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff AC
Service interface/external busbasic insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff AC
Service interface/supplybasic insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff AC
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Standard conformity
Electrical isolationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Massapprox. 505 g
Data for application in connection with Ex-areas
Statement of conformityTГњV 00 ATEX 1617 X (observe statement of conformity)
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4