MODBUS Plus gateway | KSD2-GW-MPL.485

Артикул: KSD2-GW-MPL.485
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • Connects the Remote Process Interface to the control system/PLC/PC via MODBUS Plus
  • Couples the internal CAN bus to the external MODBUS Plus
  • Device installation in Zone 2
  • Master function for the internal CAN bus
  • External bus: MODBUS Plus
  • External baud rate 1 MBd
  • Standard interface RS 485
  • Separate service connection independent from the DCS or PLC through RS 485 interface in addition to MODBUS Plus connection
  • 24 V DC supply voltage
  • Redundant gateway possible

Datasheet as PDF in following languages:


Technical Data: KSD2-GW-MPL.485

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power consumption4.8 W
Internal bus
ConnectionPower Rail
InterfaceCAN protocol via Power Rail bus with up to 125 units
Cycle time1 device 25 ms
125 devices with discrete input 60 ms
125 devices with discrete output 90 ms
125 devices with analog input 75 ms
125 devices with analog output 110 ms
External bus
Connection9-pin Sub-D socket
InterfaceMODBUS Plus, RS 485 interface
Service interface
Connectionterminals 22, 23, 24
InterfaceRS 485
Redundancy
Optionthrough the use of a second gateway
Electrical isolation
Internal/external busbasic insulation acc. to EN 50178, rated insulation voltage 50 Veff AC
Internal bus/power supplynot available
External bus/power supplybasic insulation acc. to EN 50178, rated insulation voltage 50 Veff AC
Service interface/internal busbasic insulation acc. to EN 50178, rated insulation voltage 50 Veff AC
Service interface/external busbasic insulation acc. to EN 50178, rated insulation voltage 50 Veff AC
Service interface/supplybasic insulation acc. to EN 50178, rated insulation voltage 50 Veff AC
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Explosion protection
Directive 94/9/ECEN 50021
Standard conformity
Electrical isolationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Protection degreeIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 505 g
Dimensions140 x 100 x 115 mm (5.5 x 3.9 x 4.5 in)
MountingDIN rail mounting
Data for application in connection with Ex-areas
Statement of conformityTГњV 00 ATEX 1617 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4