Transmitter Power Supply | KSD2-CI-2

Артикул: KSD2-CI-2
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 2-channel
  • 24 V DC supply voltage
  • 4 limit values per channel
  • Lead breakage (LB) and short-circuit (SC) monitoring
  • Power Rail bus
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KSD2-CI-2

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power loss1.4 W , increase up to 2.35 W in the case of short-circuit between terminals 1 and 3 or 2 and 3
Power consumption1.9 W , increase up to 2.35 W in the case of short-circuit between terminals 1 and 3 or 2 and 3
Input
Connectionterminals 1, 2, 3; 4, 5, 6
Input signal0/4 ... 20 mA
Input resistanceapprox. 105 Ω , terminals 1, 2
Transmitter supply voltage> 15 V at 20 mA
Line fault detectionbreakage I ≤ 2 mA , short-circuit U < 4 V
Output
InterfaceCAN protocol via Power Rail bus
ConnectionPower Rail
Transfer characteristics
Deviation0.1 % of the input signal range at 20 В°C (68 В°F)
Electrical isolation
Input/power supply, internal busbasic insulation acc. to EN 50178, rated insulation voltage 300 Veff
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Explosion protection
Directive 94/9/ECEN 50021
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Protection degreeIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 100 g
Dimensions20 x 100 x 115 mm (0.8 x 3.9 x 4.5 in)
MountingDIN rail mounting
Data for application in connection with Ex-areas
Statement of conformityTГњV 00 ATEX 1617 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4


Назад в раздел