1-channel Output Ex ia IIC FM approval Device installation permissible in Div. 2 24 V DC supply voltage Lead breakage (LB) and short-circuit (SC) monitoring Power Rail bus
Datasheet as PDF in following languages:
Technical Data: KSD2-CO-Ex Supply Connection Power Rail Rated voltage 20 ... 30 V DC Ripple < 10 % Power loss 1.3 W Power consumption 1.3 W Input Connection Power Rail Interface CAN protocol via Power Rail bus Output Connection terminals 2, 3 Current 0/4 ... 20 mA Load 30 ... 750 Ω Residual ripple max. 0.25 % Line fault detection possible for Inominal ≥ 1 mA breakage I < 3.6 mA, short-circuit, load < 30 Ω Transfer characteristics Deviation 0.1 % of output signal range at 20 В°C (68 В°F) Electrical isolation Output/power supply, internal bus safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V Conformity Insulation coordination IEC 60664-1 Electrical isolation IEC 60079-11 Protection degree IEC 60529 Ambient conditions Ambient temperature -20 ... 60 В°C (-4 ... 140 В°F) Damaging gas acc. to ISA-S71.04-1985, severity level G3 Mechanical specifications Protection degree IP20 Connection terminal connection ≤ 2.5 mm2 Mass approx. 100 g Dimensions 20 x 100 x 115 mm (0.8 x 3.9 x 4.5 in) Mounting DIN rail mounting