Switch Amplifier | ED2-SR-Ex8

Артикул: ED2-SR-Ex8
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 8-channel isolated barrier
  • 24 V DC supply
  • Dry contact or NAMUR inputs
  • Relay output
  • Fault indication output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Configurable via PC

Datasheet as PDF in following languages:


Technical Data: ED2-SR-Ex8

General specifications
Signal typeDigital Input
Supply
Connectiond14+, z14-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Power consumptionapprox. 4 W
Input
Connectionchannel 1: d2-, b2+
channel 2: d4-, b2+
channel 3: d6-, b4+
channel 4: d8-, b4+
channel 5: z2-, b6+
channel 6: z4-, b6+
channel 7: z6-, b8+
channel 8: z8-, b8+
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 7.5 V DC / approx. 7.5 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.15 mA , short-circuit I > 6 mA
Pulse length/pulse interval≥ 1 ms / ≥ 1 ms
Output
Connectionchannel 1: d22, d24
channel 2: d26, d28
channel 3: d30, d32
channel 4: b22, b24
channel 5: b26, b28
channel 6: b30, b32
channel 7: z22, z24
channel 8: z26, z28
Outputsignal ; relay
Contact loading60 V AC/1 A/60 VA; 60 V DC/1 A resistive load/24 W
Energized/De-energized delay5 ms / 5 ms
Mechanical life2 x 107 switching cycles
Error message output
Connectionz30, z32
Outputfault signal ; relay
Contact loading60 V AC/1 A/60 VA; 60 V DC/1 A resistive load/24 W
Energized/De-energized delay5 ms / 5 ms
Mechanical life2 x 107 switching cycles
Transfer characteristics
Switching frequency< 10 Hz
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Low voltage
Directive 2006/95/ECEN 50178:1997
Conformity
Insulation coordinationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Connection48-pin plug connector acc. to DIN 41612 , series 2 , type F , z, b and d provided
Massapprox. 175 g
Dimensions20 x 128 x 193 mm (0.8 x 5 x 7.6 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 00 ATEX 2207 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC
InputEEx ia IIC
Voltage Uo11.8 V
Current Io14.6 mA
Power Po43 mW (linear characteristic)
Electrical isolation
Input/Outputsafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Input/power supplysafe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 50014:1997, EN 50020:1994


Назад в раздел