Transmitter power supplies | KFD2-CR-Ex1.30200
Артикул: KFD2-CR-Ex1.30200
Производитель: Pepperl-Fuchs
Not available for purchase, If you need assistance please contact us sales@sm-industry.ru Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru
1-channel Input EEx ia IIC; Uo = 26 V 24 V DC nominal supply voltage Output: allowable load max. 1 kΩ EMC acc. to NAMUR NE 21
Datasheet as PDF in following languages:
Technical Data: KFD2-CR-Ex1.30200 Product Description 24 V DC: Supply Connection Power Rail or terminals 11+, 12- Rated voltage 20 ... 35 V DC Ripple within the supply tolerance Power loss 1.1 W Power consumption approx. 1.6 W Input Connection terminals 1+, 3- Available voltage 17.6 V DC at 20 mA Output Connection terminals 7-, 8+, 9- Load ≤ 1 kOhm Output signal 0 ... 20 mA or 4 ... 20 mA Ripple max. 20 µA ss Available voltage 20 V DC Transfer characteristics Rise time ≤ 50 µs ; load = 250 Ω De-energized delay ≤ 50 µs; load = 250 Ω Directive conformity Electromagnetic compatibility Directive 89/336/EEC EN 61326, EN 50081-2, NE 21 Ambient conditions Ambient temperature -20 ... 60 °C (-4 ... 140 °F) Mechanical specifications Protection degree IP20 Mass approx. 100 g Data for application in connection with Ex-areas EC-Type Examination Certificate BAS 00 ATEX 7164 ; for additional certificates refer to the approval list Group, category, type of protection II (1)GD [EEx ia] IIC (-20 °C ≤ Tamb ≤ 60 °C)Statement of conformity TUV 02 ATEX 1797 X (observe statement of conformity) Group, category, type of protection, temperature class II 3G EEx nA II T4Directive conformity Directive 94/9/EC on request
Назад в раздел