product name | closed-loop control infeed/regenerative feedback module |
Unit type | infeed module |
Function status | 1 |
Cooling | external |
cooling method | separate cooling |
degree of protection | IP 20 for the electronics area and IP 54 for the heatsink in the heat dissipation area |
weight / approx. | 10.5 kg |
dimension / width | 100 mm |
dimension / height | 480 mm |
dimension / depth | 288 mm |
infeed / type | closed-loop |
connection / power connection | 16 mm2 |
Connection / line connection / cross-section / max. | 16 mm² |
| |
|
rated output / infeed | 16 kW |
rated output / infeed / S3-60 % | 21 kW |
rated output / infeed / peak power | 35 kW |
rated output / regenerative feedback | 16 kW |
rated output / regenerative feedback / peak power | 35 kW |
rated current In | 27 A |
rated current In / Input / at undervoltage | 30 A |
Rated current In / Output / Peak current | 59 A |
Input voltage | 400 V 3-phase AC -10% to 480 V 3-phase AC + 6 % |
Output voltage | 600V / 625V / 680V |
power frequency / min. | 50 Hz |
power frequency / tolerance / min. | -10 % |
power frequency / max | 60 Hz |
power frequency / tolerance / max | 10 % |
Efficiency eta | 0.97 |
charging limit | 6000 µF |
power factor / cos phi / sine current mode | 0.98 |
power factor / cos phi / block current mode | 0.98 |
power factor / cos lambda / sine current mode | 0.97 |
power factor / cos lambda / block current mode | 0.89 |
impedance voltage / required / maximum | 3 % |
| |
|
ambient temperature on operation / min. | 0 °C |
ambient temperature / during operation / max. | 40 °C |
ambient temperature / during operation / max. / with power reduction | 55 °C |
ambient temperature / when stored / min. | -40 °C |
ambient temperature / when stored / max. | 70 °C |
ambient temperature / when transported / min. | -40 °C |
ambient temperature / when transported / max. | 70 °C |
| |
last change: | Jan 30, 2012 |