HED4
Артикул |
Наименование |
Производитель |
HED41M015
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 15 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 65 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HED41B030L
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 30 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 65 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG TERMINAL; WIRE SIZE 10 TO 4 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED43B020L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 20 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED41B025L
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 25 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 65 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG TERMINAL; SIZE 1 INCH W X 4.56 INCH D X 6.35 INCH H; APPROVAL UL 489, CSA 22.2 _
|
Siemens
|
HED43B070SN
|
70A 3P 480VAC CB _
|
Siemens
|
HED41B045L
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG TERMINAL; WIRE SIZE 10 TO 4 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED41M045
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED42M030
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 30 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED43B015
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 15 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG LOAD TERMINAL TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HED43M100LBESN
|
CIRCUIT BREAKER, THERMAL MAGNETIC; 3 POLE; 480 VAC; 100 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC; LINE LUG, LOAD LUG TERMINAL; WIRE SIZE 2/0 AWG (COMPRESSION LUG) _
|
Siemens
|
HED41B090
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 90 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG LOAD TERMINAL TERMINAL; WIRE SIZE 4 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED42B045L
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC (UL); LUG TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED42B020L
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 20 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC (UL); LUG TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HHED63B090LAE
|
CIRCUIT BREAKER, THERMAL MAGNETIC; 3 POLE; 480 VAC; 90 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC; LINE LUG, LOAD LUG TERMINAL; WIRE SIZE 2/0 AWG (COMPRESSION LUG) _
|
Siemens
|
HED43M045
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED41M020
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 20 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 65 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HED43B030L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 30 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC; LINE LUG, LOAD LUG TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER, LOAD); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED41B045
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 4 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED43M080
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 80 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED43B070L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 70 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED42M020
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 20 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HED42M080
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 80 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED43B025
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 25 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG LOAD TERMINAL TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER) _
|
Siemens
|
HED43B025L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 25 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED43B045L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 45 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED42B100L
|
THERMAL MAGNETIC; 2 POLE; 480 VAC, 250 VDC; 100 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC, 30 KILOAMPERE AT 250 VDC (UL); LUG TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED43B025L
|
THERMAL MAGNETIC; 3 POLE; 480 VAC; 25 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 240 VAC, 42 KILOAMPERE AT 480 VAC (UL); LUG TERMINAL; WIRE SIZE 12 TO 10 AWG (ALUMINUM), 14 TO 10 AWG (COPPER); SIZE 3 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
HED41B035L
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 35 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG TERMINAL; WIRE SIZE 10 TO 4 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED41M040
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 40 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 25 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC; LUG LOAD TERMINAL TERMINAL; WIRE SIZE 10 TO 1/0 AWG (ALUMINUM/COPPER) _
|
Siemens
|
HED41B020
|
THERMAL MAGNETIC; 1 POLE; 277 VAC, 125 VDC; 20 AMPERE AT 40 DEG C; INTERRUPTING RATING 100 KILOAMPERE AT 120 VAC, 65 KILOAMPERE AT 277 VAC, 30 KILOAMPERE AT 125 VDC (UL); LUG LOAD TERMINAL TERMINAL; SIZE 1 INCH W X 4.56 INCH D X 6.35 INCH H _
|
Siemens
|
Товары
151 - 180 из 203
Начало
|
Пред.
|
1
2
3
4
5
6
7
|
След. |
Конец