ADJUSTABLE TRIP, MOLDED CASE, THERMAL MAGNETIC; FD FRAME; 600 VAC AT 50/60 HZ, 250 VDC; 250 AMPERE AT 40 DEG C; 2 POLE; TRIP SETTING 1100 TO 2500 AMPERE; TERMINAL NOT INCLUDED; FXD6 MODEL _

Артикул: FXD62B250
Производитель: Siemens


FXD62B250

Product Details

Catalog Number:FXD62B250
Manufacturer:Siemens
Connection:Bolt-on
Frame Type:FXD
Amperage:250
Poles:2
Voltage:600<
Full Description:ADJUSTABLE TRIP, MOLDED CASE, THERMAL MAGNETIC; FD FRAME; 600 VAC AT 50/60 HZ, 250 VDC; 250 AMPERE AT 40 DEG C; 2 POLE; TRIP SETTING 1100 TO 2500 AMPERE; TERMINAL NOT INCLUDED; FXD6 MODEL
Download the Catalog Data-Sheet PDF

Additional Details

Directory:CIS
Commerce Sector:Construction Materials
Industry:Electrical
Commodity Code:3220
Commodity Description:Circuit Breakers - Commercial Circuit Breakers
Noun:Circuit Breaker
UPC:78364321118
Item Number:21118
Catalog Number:FXD62B250
MSDS Form Number:*
UNSPSC:30212000
Image Location:Circuit Breaker Image
Model:FXD6
Type:ADJUSTABLE TRIP, MOLDED CASE, THERMAL MAGNETIC
Frame Type:FD
Voltage Rating:600 VAC AT 50/60 HZ, 250 VDC
Maximum AC Voltage Rating:600
Maximum AC Voltage Rating - UOM:V
Maximum DC Voltage Rating:250
Maximum DC Voltage Rating - UOM:V
Current Rating:250 AMPERE AT 40 DEG C
Number of Poles:2
Trip Setting:1100 TO 2500 AMPERE
Terminal Type:NOT INCLUDED
kAIC Ratings:65 KAIC at 240 Volts 35 KAIC at 480 Volts 22 KAIC at 600 VAC
Lugkit:TA1FD350A = #4
Mounting Hardware:FC1, FCII, CDP5, CDP6, S5, P5 = 6F62 or 6F6D SPP Shallow, S4 or P4 = SE6
Common Accessories:S01FD60 = 120 VAC Shunt Trip U01FD60 = 120 VAC UVR A01FD62 = 1 N/O auxilary Switch and 1 N/C Auxilary Switch