********************************************************** Description: TOOLBOX II Version 4 Itemnumber: S38-100 Revision: V04.10_SP03 Date of Release: 2010-03-29 ********************************************************** ********************** *--- NEW FEATURES ---* ********************** AU Up-/Download Through the Upload function all engineering data of an ACP 1703 component can be stored directly in the destination system. During loading of the automation unit these data are automatically stored on the flashcard of the automation unit. Later the user can read back these data from the destination system into a TOOLBOX II-PC. *************************** *--- FAULT CORRECTIONS ---* *************************** 1703 GENERAL ------------ * Enhancement PLC-Code for TM 1703 emic (CHDOC00021790) Enhancement PLC-Code for TM 1703 emic: old value max. 64kB, new value 128kB * Support of TM 1703 mic CPC60 Rev. 21 (CHDOC00008168) * Support of TM 1703 mic CPC60 Rev. 22 (CHDOC00022258) Flash-Loader ------------ * Bugfix when firmware loading of several AMIS-DC AUs (CHDOC00008166) After selecting and loading of several AUs not all AUs are displayed in window "PSRII firmware loading: Edit AUs". IEC 61850 Read-in SCL files --------------------------- * Bugfix when generating an ICD-file (GOOSE definition) (CHDOC00008185) GOOSE data are exported not correctly for all logical devices * Bugfix when generating an ICD-file (report control blocks) (CHDOC00008187) Amount of report control blocks is not always correct (default value!). BC 1703 ACP picture parametrization ----------------------------------- * Bugfix when transforming BC 1703 ACP (CHDOC00008172) Error message when generating assignments for picture parametrization after installation of service pack 2. * Bugfix exchange of assignments (picure parametrization, AU-Copy) (CHDOC00021879) Process technical address of image is not correct and cannot be changed (wizard to exchange assignments of picture parametrization) * Bugfix event list/Update TBII V04.10_SP02 (CHDOC00021924) After updating TBII V04.10_SP02 all messages, which were used in TBII V04.10_SP01 additionally as events are now set to "no" instead of "yes" in event list! * Bugfix in event list view - full texts (index) (CHDOC00021925) * BC 1703 ACP Display - suppress event list messages (CHDOC00022174) Error description: From TBII V04.10 SP2 it is possible to activate or suppress messages in event list display (show yes/no). After parameter setting "no" these messages are still activated in event list. When saving, transforming and comparing with parameter loader all parameter are however up to date. CAEx plus --------- * CAEx plus start problems with a equipped TM 1703 emic/CPC30 AU (CHDOC00021777) CAEx plus cannot not be started with more than one configured TM 1703 emic/CPC30. For each AU an exception occurs first time of creation in CAEx plus project tree. OPM II ------ * Bugfix when transforming ET03 (CHDOC00008174) Error message when transforming "Missing IED name in system element" and no GOOSE parameter setting * GW-Main exception (CHDOC00008062) Bugfix of GW-Main-Exception after different user interactions * ICD file generation doesn't work with not configured ET03 on M-CPU (CHDOC00022159) ICD-file generation: If ET03 (IEC61850-protocol element - corresponds to an IED) is configured on C-CPU, generation doesn't work. Error message: "no corresponding link images found!". Data Distribution Center ------------------------ * Exception when importing ranges with identical signal names (CHDOC00022262) Exception when importing ranges with identical signal names. This signals are used already in a different range of the process-technical plant. ****************************************** *--- Installation of the service pack ---* ****************************************** The installation is performed by starting "4_10_0003.exe" from the root directory of the data medium or after download from the corresponding directory. This Service Pack has to be installed on client and server. Note: When working with network databases (peer server) it is necessary to install the same TOOLBOX II- Version on all clients and the server. (to prevent database revisions problems!) How is it detected whether a service pack has been installed? After the installation of a service pack the current service pack number is displayed in the tools startup window.