6ES7 350-2AH01-0AE0

Supply voltages

 

Aux. voltage 1L+, load voltage 2 L+

 

  • Rated value (DC)

24 V

  • permissible range, lower limit (DC)

20.4 V

  • permissible range, upper limit (DC)

28.8 V

Current consumption

 

from load voltage L+ (without load), max.

150 mA

from backplane bus 5 V DC, max.

100 mA

Power losses

 

Power loss, typ.

10 W

Connection method

 

required front connector

1x 40-pin

Digital inputs

 

Number of digital inputs

8

Functions

1 each for gate start/ gate stop

Input voltage

 

  • for signal "0"

-3 to +5 V

  • for signal "1"

11 to 30.2 V

Input current

 

  • for signal "0", max. (permissible quiescent current)

2 mA

  • for signal "1", typ.

9 mA

Input delay (for rated value of input voltage)

 

  • for standard inputs

 

    • at "0" to "1", max.

50 µs

Cable length

 

  • Cable length, shielded, max.

100 m

Digital outputs

 

Number of digital outputs

8

Short-circuit protection

Yes

Limitation of inductive shutdown voltage to

L+ (-40 V)

Output voltage

 

  • for signal "1", min.

L+ (-0.8 V)

Output current

 

  • for signal "1" rated value

0.5 A

  • for signal "0" residual current, max.

0.5 mA

Output delay with resistive load

 

  • 0 to "1", max.

300 µs

Switching frequency

 

  • with resistive load, max.

500 Hz

  • with inductive load, max.

0.5 Hz

Aggregate current of outputs (per group)

 

  • horizontal installation

 

    • up to 40 °C, max.

4 A

    • up to 60 °C, max.

2 A

  • all other mounting positions

 

    • up to 40 °C, max.

2 A

Cable length

 

  • Cable length, shielded, max.

600 m

  • Cable length unshielded, max.

100 m

Encoder supply

 

Output voltage

NAMUR-encoder supply: 8.2 V +/-2%

Output current, rated value

200 mA

Short-circuit protection

Yes

Encoder

 

Connectable encoders

 

  • Incremental encoder (asymmetrical)

Yes

  • 24 V initiator

Yes

  • 24 V directional element

Yes

  • NAMUR encoder

Yes

  • 2-wire BEROS

Yes

NAMUR encoder

 

  • Number of NAMUR inputs

8

  • Input signal

to DIN 19 234

  • Input current, for signal "0", max.

1.2 mA

  • Input current, for signal "1", min.

2.1 mA

  • Input delay, max.

50 µs

  • Input frequency, max.

20 kHz

  • Cable length, shielded, max.

100 m

Counter

 

Counter input 24 V

 

  • Number

8; 32 bit or +/-31 bit

  • Input voltage, for signal "0"

-3 to +5 V

  • Input voltage, for signal "1"

11 to 30.2 V

  • Input current, for signal "0", max. (permissible quiescent current)

2 mA

  • Input current, for signal "1", typ.

9 mA

  • Input delay, max.

50 µs

  • Counter frequency, max.

20 kHz; Incremental encoder: 10 kHz

  • Cable length, max.

100 m

Interrupts/diagnostics/status information

 

Alarms

 

  • Diagnostic alarm

Yes; Parameterizable

  • Process alarm

Yes; Parameterizable

Diagnoses

 

  • Diagnostic functions

Yes; Diagnostic information readable

Galvanic isolation

 

Galvanic isolation digital inputs

 

  • between the channels and the backplane bus

Yes; and shielding

  • between the channels and the backplane bus (NAMUR)

yes, against backplane bus and shielding

Galvanic isolation digital outputs

 

  • between the channels and the backplane bus

Yes; and shielding

Galvanic isolation counter

 

  • between the channels and the backplane bus

Yes; and shielding

Dimensions and weight

 

Dimensions

 

  • Width

80 mm

  • Height

125 mm

  • Depth

120 mm

Weight

 

  • Weight, approx.

460 g