6ES7 417-4XT05-0AB0

Product version

 

Firmware version

V5.0

associated programming package

STEP7 V 5.3 SP2 or higher with HW update

Supply voltages

 

Feeding of external backup voltage to CPU

5 to 15 VDC

Current consumption

 

from backplane bus 5 V DC, max.

1.8 A

Power losses

 

Power loss, max.

6 W

Backup battery

 

Battery operation

 

  • Backup current, typ.

225 µA; Valid up to 40°C

  • Backup current, max.

750 µA

Memory

 

Work memory

 

  • integrated (for program)

15 Mbyte

  • integrated (for data)

15 Mbyte

  • expandable

No

Load memory

 

  • expandable FEPROM

Yes

  • expandable FEPROM, max.

64 Mbyte

  • integrated RAM, max.

1 Mbyte

  • expandable RAM

Yes

  • expandable RAM, max.

64 Mbyte

Backup

 

  • present

Yes

  • with battery

Yes

  • without battery

No

CPU/ blocks

 

DB

 

  • Number, max.

16 000; Number range: 1 to 16,000

  • Size, max.

64 Kibyte

FB

 

  • Number, max.

8 000; Number range: 0 to 7999

  • Size, max.

64 Kibyte

FC

 

  • Number, max.

8 000; Number range: 0 to 7999

  • Size, max.

64 Kibyte

OB

 

  • Size, max.

64 Kibyte

Nesting depth

 

  • per priority class

24

  • additional within an error OB

2

CPU processing times

 

for bit operations, min.

18 ns

for word operations, min.

18 ns

for fixed point arithmetic, min.

18 ns

for floating point arithmetic, min.

54 ns

Counters, timers and their retentivity

 

S7 counter

 

  • Number

2 048

  • Retentivity

 

    • can be set

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

Z 0 to Z 7

  • Counting range

 

    • lower limit

0

    • upper limit

999

IEC counter

 

  • present

Yes

  • Type

SFB

S7 times

 

  • Number

2 048

  • Retentivity

 

    • can be set

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

No times retentive

  • Time range

 

    • lower limit

10 ms

    • upper limit

9 990 s

IEC timer

 

  • present

Yes

  • Type

SFB

Data areas and their retentivity

 

retentive data area, total

Total working and load memory (with backup battery)

Flag

 

  • Number, max.

16 Kibyte

  • Retentivity available

Yes

  • Number of clock memories

8; (in 1 memory byte)

Data blocks

 

  • Number, max.

16 000; Number range: 1 to 16,000

  • Size, max.

64 Kibyte

Local data

 

  • adjustable, max.

64 Kibyte

  • preset

32 Kibyte

Address area

 

I/O address area

 

  • overall

16 Kibyte

  • Outputs

16 Kibyte

  • of which, distributed

 

    • MPI/DP interface, inputs

2 Kibyte

    • MPI/DP interface, outputs

2 Kibyte

    • DP interface, inputs

8 Kibyte

    • DP interface, outputs

8 Kibyte

Process image

 

  • Inputs, adjustable

16 Kibyte

  • Outputs, adjustable

16 Kibyte

  • Inputs, default

1 024 byte

  • Outputs, default

1 024 byte

  • consistent data, max.

244 byte

  • Access to consistent data in process image

Yes

Subprocess images

 

  • Number of subprocess images, max.

15

Digital channels

 

  • Inputs

131 072

  • Outputs

131 072

  • Inputs, of which central

131 072

  • Outputs, of which central

131 072

Analog channels

 

  • Inputs

8 192

  • Outputs

8 192

  • Inputs, of which central

8 192

  • Outputs, of which central

8 192

Hardware configuration

 

connectable OPs

63

Central devices, max.

1

Expansion devices, max.

21

Multicomputing

Yes; 4 CPUs max. (with UR1 or UR2)

Interface modules

 

  • Number of connectable IMs (total), max.

6

  • Number of connectable IM 460s, max.

6

  • Number of connectable IM 463s, max.

4; IM 463-2

Number of DP masters

 

  • integrated

2

  • via IM 467

4

  • via CP

10; CP 443-5 Extended

  • Mixed mode IM + CP permitted

No; IM 467 cannot be used with CP 443-5 Ext.; IM 467 cannot be used with CP 443-1 EX40 in PN IO mode

  • via interface module

2

  • Number of pluggable S5 modules (via adapter capsule in central device), max.

6

Number of IO Controllers

 

  • via CP

4; Via CP 443-1 EX 41 in PN mode; max. 4 in central controller

Number of operable FMs and CPs (recommended)

 

  • FM

Limited by number of slots and number of connections

  • CP, point-to-point

Limited by number of slots and number of connections

  • PROFIBUS and Ethernet CPs

14; Of which 10 CP or IM max. as DP master and PN controller

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

  • battery-backed and synchronizable

Yes

  • Resolution

1 ms

Runtime meter

 

  • Number

8

Clock synchronization

 

  • supported

Yes

  • to MPI, master

Yes

  • to MPI, slave

Yes

  • to DP, master

Yes

  • to DP, slave

Yes

  • in AS, master

Yes

  • in AS, slave

Yes

  • on Ethernet via NTP

Via CP

  • to IF 964 DP

Yes

S7 message functions

 

Number of login stations for message functions, max.

63; Max. 63 with ALARM_S and ALARM_D (OPs); max. 16 with ALARM_8 and ALARM_P (e.g. WinCC)

Symbol-related messages

Yes

Number of messages

 

  • overall, max.

1 024

Block related messages

Yes

Alarm 8-blocks

Yes

Process control messages

Yes

Test commissioning functions

 

Status/control

 

  • Status/control variable

Yes

Forcing

 

  • Forcing

Yes

Status block

Yes

Single step

Yes

Number of breakpoints

4

Diagnostic buffer

 

  • present

Yes

  • Number of entries, max.

3 200

    • can be set

Yes

    • preset

120

Communication functions

 

PG/OP communication

Yes

Routing

Yes

Global data communication

 

  • supported

Yes

  • Size of GD packets, max.

54 byte

S7 basic communication

 

  • supported

Yes

  • User data per job, max.

76 byte

S7 communication

 

  • supported

Yes

  • User data per job, max.

64 Kibyte

S5-compatible communication

 

  • supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

  • User data per job, max.

8 Kibyte

Standard communication (FMS)

 

  • supported

Yes; Via CP and loadable FB

Web server

 

  • supported

No; Via CP

Open IE communication

 

  • ISO-on-TCP (RFC1006)

Via CP 443-1 Adv. and loadable FB

    • Data length, max.

1452

Number of connections

 

  • overall

64

1st interface

 

Type of interface

Integrated

Physics

RS 485 / PROFIBUS

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

MPI: 44, DP: 32

Functionality

 

  • MPI

Yes

  • DP master

Yes

  • DP slave

Yes

MPI

 

  • Number of connections

44

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

Yes

    • S7 basic communication

Yes

    • S7 communication

Yes

  • Transmission rate, max.

12 Mbit/s

DP master

 

  • Number of connections, max.

32

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

No

    • S7 basic communication

Yes

    • S7 communication

Yes

    • Equidistance mode support

Yes

    • SYNC/FREEZE

Yes

    • Activation/deactivation of DP slaves

Yes

    • Direct data exchange (slave-to-slave communication)

Yes

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

32

  • Address area

 

    • Inputs, max.

2 Kibyte

    • Outputs, max.

2 Kibyte

  • User data per DP slave

 

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

DP slave

 

  • Number of connections

32

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

  • GSD file

http://support.automation.siemens.com/WW/view/de/113652

  • Transmission rate, max.

12 Mbit/s

  • Transfer memory

 

    • Inputs

244 byte

    • Outputs

244 byte

  • Address area, max.

32

  • User data per address area, max.

32 byte

  • User data per address area, of which consistent, max.

32 byte

2nd interface

 

Type of interface

Integrated

Physics

RS 485 / PROFIBUS

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

32

Functionality

 

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of connections, max.

32

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

No

    • S7 basic communication

Yes

    • S7 communication

Yes

    • Equidistance mode support

Yes

    • SYNC/FREEZE

Yes

    • Activation/deactivation of DP slaves

Yes

    • Direct data exchange (slave-to-slave communication)

Yes

  • Transmission speeds, max.

12 Mbit/s

  • Number of DP slaves, max.

125

  • Address area

 

    • Inputs, max.

8 Kibyte

    • Outputs, max.

8 Kibyte

  • User data per DP slave

 

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

DP slave

 

  • Number of connections

32

  • Services

 

    • Routing

Yes

    • Programming

Yes

  • GSD file

http://support.automation.siemens.com/WW/view/de/113652

  • Transmission rate, max.

12 Mbit/s

  • Transfer memory

 

    • Inputs

244 byte

    • Outputs

244 byte

  • Address area, max.

32

  • User data per address area, max.

32 byte

  • User data per address area, of which consistent, max.

32 byte

3rd interface

 

Type of interface

Pluggable interface module (IF), technical specifications as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

4th interface

 

Type of interface

Pluggable interface module (IF), technical specifications as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Isochronous mode

 

Isochronous mode

Yes

User data per isochronous slave, max.

244 byte

equidistance

Yes

shortest clock pulse

1 ms; 0.5 ms without use of SFC 126, 127

max. cycle

32 ms

CiR - Configuration in RUN

 

CiR synchronization time, basic load

100 ms

CiR synchronization time, time per I/O slave

40 µs

CPU/ programming

 

Configuration software

 

  • STEP 7

Yes

Programming language

 

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

Yes

  • GRAPH

Yes

  • HiGraph®

Yes

Nesting levels

7

Know-how protection

 

  • User program protection/password protection

Yes

Dimensions

 

Required slots

2

Dimensions and weight

 

Dimensions

 

  • Width

50 mm

  • Height

290 mm

  • Depth

219 mm

Weight

 

  • Weight, approx.

920 g